PropertyShield Report — Stonegate Mills Apartments (2 Millpond Lane, Tarrytown, NY)
2 Millpond Lane, Tarrytown, NY 10591
Review of the provided records and photos for Stonegate Mills (42-unit multifamily) shows an active recurring plumbing failure on the building B-line waste stack that led to an overnight emergency (June 2026) with water into Unit 2B and the 2nd-floor hallway. That event was mitigated by an emergency plumber and United Restoration Services, but the original plumber's recommendation of a camera inspection of the shared stack remains open.
Additional readiness gaps were identified: staff are unsure where the main building water shutoff is located, and there is no documented lockbox/key procedure for after-hours access. Equipment and compliance documentation (elevator cat-1, roof warranty, boiler service agreement and combustion report) is on file, while the backflow test on file shows a past-due next-test date. Several operational items (boiler circulator wear, roof drain clearing after storms, and recorded water-usage spikes) need follow-up.
This report lists the findings in priority order with practical next steps; every fact it cites was reviewed by URS against the source documents.
Priority handoff
What happens next
You choose the path for every item. The available options are shown with each priority, and you stay in control.
Recurring B-line waste-stack failures affecting units 2B/3B/4B
crossriver-invoice-1.pdf (Mar 1, 2025) — documented pinhole leak and patch at cast-iron B-line branch crossriver-invoice-2.pdf (Oct 28, 2025) — invoice and written recommendation for camera inspection crossriver-invoice-3.pdf (June 2026) — after-hours emergency invoice describing stack failure and active water into 2B and hallway maintenance-ticket-log.xlsx entries (2025-10-24, 2026-06-08) showing emergency calls and open camera recommendation resident-email-3B-leak.pdf (June 13, 2026) — tenant report of overnight water and wet hallway unit-2B-ceiling-patch.jpg — visible patch and evidence of prior ceiling repair urs-mitigation-work-order.pdf (June 16, 2026) — emergency extraction and drying equipment deployed
Evidence: crossriver-invoice-3.pdf, page 1Have building staff keep the cleanout and affected areas accessible, assign the recommended camera inspection, and record the result and permanent next step.
Email to: in-house or on-site staffOpen internal emailHave on-site staff share the service history and arrange the camera inspection directly with your plumber or drain specialist.
Email to: on-site staff + plumber or drain specialistOpen staff + vendor emailAsk URS to coordinate with your building team and plumber or drain specialist and capture the inspection and completed-work records.
Email to: United Restoration Services onlyOpen URS emailUnknown/poorly-documented main building water shutoff and access gaps
ray-note-shutoff.jpg — handwritten note: 'main shutoff — behind elec panel in old loading dock?? ask Ray (check before next leak!!)' stonegate-mills-floor-plan-1988.pdf — plan notes domestic water service enters at basement mechanical room, north end (no unit isolation valves shown) old-loading-dock-panel.heic and photos of old loading dock area (evidence of electrical panels near loading dock)
Evidence: ray-note-shutoff.jpg, page 1Have your building team handle the repair. After it is resolved, do not forget to update your PropertyShield records.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your in-house or on-site staff and the appropriate plumber or vendor.
Email to: on-site staff + plumber or appropriate vendorOpen staff + vendor emailAsk URS to manage coordination with the people involved and capture the completed repair record.
Email to: United Restoration Services onlyOpen URS emailOpen recommendation: camera inspection of shared waste stack (Crossriver recommendation)
crossriver-invoice-2.pdf — technician recommendation and estimate note for camera inspection maintenance-ticket-log.xlsx shows the camera inspection recommendation ticket as OPEN
Evidence: crossriver-invoice-2.pdf, page 2Have building staff keep the cleanout and affected areas accessible, assign the recommended camera inspection, and record the result and permanent next step.
Email to: in-house or on-site staffOpen internal emailHave on-site staff share the service history and arrange the camera inspection directly with your plumber or drain specialist.
Email to: on-site staff + plumber or drain specialistOpen staff + vendor emailAsk URS to coordinate with your building team and plumber or drain specialist and capture the inspection and completed-work records.
Email to: United Restoration Services onlyOpen URS emailBuilding-level water usage spikes (Mar–Jun 2026) that correlate to maintenance events
water-bill-baseline.pdf (Jan 23, 2026) — usage 118 HCF baseline water-bill-spike.pdf (Mar 22, 2026) — usage 151 HCF (notable spike) water-bill-recent.pdf (Jun 30, 2026) — usage 139 HCF maintenance-ticket-log.xlsx entries (water events, plumbing calls, June 2026 emergency)
Evidence: water-bill-spike.pdf, page 1Have your building team handle the repair. After it is resolved, do not forget to update your PropertyShield records.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your in-house or on-site staff and the appropriate plumber or vendor.
Email to: on-site staff + plumber or appropriate vendorOpen staff + vendor emailAsk URS to manage coordination with the people involved and capture the completed repair record.
Email to: United Restoration Services onlyOpen URS emailActive water intrusion event (June 2026) with mitigation completed but follow-up required
crossriver-invoice-3.pdf (after-hours emergency) — leak description, riser shut at basement cleanout, time stamps urs-mitigation-work-order.pdf — emergency extraction, drying equipment and moisture monitoring visits, dry standard confirmed maintenance-ticket-log.xlsx (2026-06-08, 2026-06-13) — emergency plumbing & URS mitigation entries resident-email-3B-leak.pdf — tenant notification thanking response unit-2B-ceiling-patch.jpg — ceiling patch evidence
Evidence: urs-mitigation-work-order.pdf, page 1Have your building team handle the repair. After it is resolved, do not forget to update your PropertyShield records.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your in-house or on-site staff and the appropriate plumber or vendor.
Email to: on-site staff + plumber or appropriate vendorOpen staff + vendor emailAsk URS to manage coordination with the people involved and capture the completed repair record.
Email to: United Restoration Services onlyOpen URS emailBackflow prevention (RPZ) annual test past due
backflow-test-cert.pdf (Test Date: May 24, 2025 — PASS; next annual test due May 24, 2026) and backflow-test-cert-prior-year.pdf (May 23, 2024) rpz-device-tag.heic — photo of device & tag
Evidence: backflow-test-cert.pdf, page 1Have your building team review this item, choose the next step, and update your PropertyShield records afterward.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your on-site staff and the appropriate vendor.
Email to: on-site staff + appropriate vendorOpen staff + vendor emailAsk URS to coordinate with the people involved and capture the completed record.
Email to: United Restoration Services onlyOpen URS emailBoiler equipment — model & serial documented; combustion PASS but circulator bearing wear noted
boiler-nameplate.heic (Foundry Ridge FR-240, Serial FR-24-09-3317, manufacture 06/2009) boiler-permit-card-2009.jpg (installation record, 2009) kestrel-combustion-report.pdf (Nov 22, 2025) — PASS but circulator pump bearing wear noted; vendor recommends scheduling replacement kestrel-service-agreement.pdf (covers FR-240, term Jan 30, 2026–Jan 30, 2027)
Evidence: kestrel-combustion-report.pdf, page 1Have your building team review this item, choose the next step, and update your PropertyShield records afterward.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your on-site staff and the appropriate vendor.
Email to: on-site staff + appropriate vendorOpen staff + vendor emailAsk URS to coordinate with the people involved and capture the completed record.
Email to: United Restoration Services onlyOpen URS emailInsurance declarations show building coverage but high water-damage deductible
property-policy-declarations.pdf — commercial package declarations; building limit $11,400,000; water damage deductible: $25,000
Evidence: property-policy-declarations.pdf, page 1Have your building team review this item, choose the next step, and update your PropertyShield records afterward.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your on-site staff and the appropriate vendor.
Email to: on-site staff + appropriate vendorOpen staff + vendor emailAsk URS to coordinate with the people involved and capture the completed record.
Email to: United Restoration Services onlyOpen URS emailRoof membrane condition and drains (warranty & recent seam repair)
roof-membrane-warranty.pdf (Van Doren Warranty — installed June 2019; warranty expires June 2029) vandoren-roof-repair-invoice.pdf (June 25, 2025) — wind-lifted seam repaired NE corner roof-membrane-drains.jpg and roof-access-hatch.jpg — photos of drains and roof access ray-note-roof-drain.jpg — staff note to clear north roof drain after big storms (leaf load)
Evidence: roof-membrane-warranty.pdf, page 1Have building staff inspect the roof drain and decide whether roof repair should be performed. Update your PropertyShield records afterward.
Email to: in-house or on-site staffOpen internal emailHave on-site staff share the location and work-order history with your roofer and arrange the follow-up directly.
Email to: on-site staff + rooferOpen staff + vendor emailAsk URS to coordinate with your building team and roofer and capture the completed repair record.
Email to: United Restoration Services onlyOpen URS emailElectrical distribution labeling & basement panel directories (done) — confirm main breaker labeling
two-rivers-panel-invoice.pdf (Feb 24, 2026) — re-label basement distribution panels; verify circuit directory accuracy electrical-panel-labeled.jpg and old-loading-dock-panel.heic — panel photos
Evidence: electrical-panel-labeled.jpg, page 1Have your building team handle the repair. After it is resolved, do not forget to update your PropertyShield records.
Email to: in-house or on-site staffOpen internal emailArrange the follow-up directly with your in-house or on-site staff and the appropriate plumber or vendor.
Email to: on-site staff + plumber or appropriate vendorOpen staff + vendor emailAsk URS to manage coordination with the people involved and capture the completed repair record.
Email to: United Restoration Services onlyOpen URS email20 readiness checks
What is confirmed, and what still needs work
These checks cover emergency access, water control, critical records and follow-through. A check counts only when current evidence confirmed by URS supports it. Missing or outdated proof stays open so nothing important disappears behind the percentage.
Can your team act fast?
5 of 6One item openCan water be found and stopped?
1 of 43 items openAre critical records current?
3 of 4One item openAre fixes documented and closed?
1 of 2One item openA service credit toward URS restoration invoices
Readiness Response Credit
Each item URS verifies adds about $90.00 to this building's response credit, up to $4,125.00 fully verified.
Your readiness checklist
All 20 checks at a glance
Select a linked evidence reference to open the customer-visible source file.
Response and access
5 of 6 confirmedRA-01 · Onsite incident lead
Current evidence has been reviewed and confirmed.
Evidence: Intake submission — Dana Whitfield (manager) and Ray Otero (superintendent) with direct linesRA-02 · After-hours escalation chain
Current evidence has been reviewed and confirmed.
Evidence: Intake submission — after-hours contact chain: Ray, then Dana, then the management lineRA-03 · Restoration and critical-trade response contacts
Current evidence has been reviewed and confirmed.
Evidence: vendor-contact-list.xlsx, page 1RA-04 · After-hours entry and key/access process
No documented lockbox or key process; manager to confirm and write it down.
Next: Document exactly how a responder gets inside after hours.RA-05 · Crew arrival, parking, staging, and service route
Current evidence has been reviewed and confirmed.
Evidence: Intake submission — arrival, staging and the loading-dock service routeRA-06 · Current floor plan or equivalent response map
Current evidence has been reviewed and confirmed.
Evidence: stonegate-mills-floor-plan-1988.pdf, page 1Water control and containment
1 of 4 confirmedWC-01 · Main domestic-water shutoff
Only an unconfirmed handwritten note places the main shutoff behind the loading-dock electrical panel. Needs locating, a photo, and a label.
Next: Locate, photograph, and label the main shutoff.WC-02 · Shutoffs are mapped by zone, riser, and branch
No riser or branch isolation map exists; the B-line stack history is exactly why one matters.
Next: Map isolation points to their served areas.WC-03 · Known water-risk areas and recurring locations
Current evidence has been reviewed and confirmed.
Evidence: resident-email-2B-damp.pdf, page 1Evidence: maintenance-ticket-log.xlsx, page 1Evidence: crossriver-invoice-3.pdf, page 1WC-04 · Leak detection covers the building's known risk areas
No leak detection installed; reviewer designates the B-line stack zone for assessment.
Next: Document zone-level detection coverage and status.Documents and systems
3 of 4 confirmedDS-01 · Applicable critical-document register
Current evidence has been reviewed and confirmed.
Evidence: elevator-cat1-cert.pdf, page 1Evidence: property-policy-declarations.pdf, page 1DS-02 · Critical inspection and compliance records are current
Backflow test expired May 2026; the most frequent vendor's COI is missing.
Next: Replace, renew, or confirm outstanding documents.DS-03 · Critical equipment, ownership, and maintenance details are documented
Current evidence has been reviewed and confirmed.
Evidence: boiler-permit-card-2009.jpg, page 1Evidence: water-heater-nameplate.heic, page 1Evidence: boiler-nameplate.heic, page 1DS-04 · Critical systems follow one current maintenance schedule
Current evidence has been reviewed and confirmed.
Evidence: kestrel-combustion-report.pdf, page 1Evidence: elevator-cat1-cert.pdf, page 1Evidence: kestrel-service-agreement.pdf, page 1Incident learning and follow-through
1 of 2 confirmedFT-01 · Prior water incidents are organized into one history
Current evidence has been reviewed and confirmed.
Evidence: maintenance-ticket-log.xlsx, page 1Evidence: crossriver-invoice-1.pdf, page 1FT-02 · Open readiness findings have an owner and disposition
First report: open findings do not yet have assigned owners and dispositions.
Next: Assign ownership and the next status.Your Instant Readiness Diagnostic was the starting point. Your answers to the nine-question quiz produced the PropertyShield Readiness Score and pointed URS toward likely gaps. Verified Readiness Attainment separately shows how many of the building's 20 readiness checks are supported by current evidence confirmed by URS. The two results stay separate because they use different inputs.
Your next progress review
What your annual review adds
This Readiness Report establishes today’s baseline. The annual review will compare progress against it without blending the two readiness measures.
Revisit the nine-question Readiness Score and the 20 evidence-confirmed readiness checks against today's starting point.
Record repairs, updated maps, current documents, and closed priorities so the value is visible.
Identify what remains open and agree on the next customer-led or URS-coordinated steps.
PropertyShield Pro with Matterport annual service: all your current building data run through our proprietary RiskSignal engine; a full report build, audit and authorization performed by a URS pro; a new report created for comparison with the original report; your live Emergency Action App and secure Building File; an annual onsite readiness inspection; a new annotated floor plan showing documented updates; and refreshed Matterport documentation.
Kept current
Readiness assets and deadlines
The records and installed controls that support the response plan.
Next due (from inspection)
CurrentNext due May 23, 2025
Evidence: backflow-test-cert-prior-year.pdf, page 1Next due (from inspection)
CurrentNext due May 24, 2026
Evidence: backflow-test-cert.pdf, page 1Next due (from inspection)
CurrentNext due Aug 26, 2026
Evidence: elevator-cat1-cert.pdf, page 1Next due (from inspection)
CurrentNext due Nov 22, 2026
Evidence: kestrel-combustion-report.pdf, page 1Policy expires (from insurance)
CurrentNext due Dec 29, 2026
Evidence: kestrel-coi.pdf, page 1Next due (from other)
CurrentNext due Jan 30, 2027
Evidence: kestrel-service-agreement.pdf, page 1Policy expires (from insurance)
CurrentNext due Feb 27, 2027
Evidence: sentry-ridge-coi.pdf, page 1Policy expires (from insurance)
CurrentNext due Mar 28, 2027
Evidence: property-policy-declarations.pdf, page 1Next due (from inspection)
CurrentNext due May 28, 2027
Evidence: fire-alarm-inspection-cert (1).pdf, page 1Warranty expires (from warranty)
CurrentNext due Jun 1, 2029
Evidence: roof-membrane-warranty.pdf, page 1Emergency response plan
Needs Expiration DateSprinkler inspection
Needs Expiration DateFire alarm inspection
Needs Expiration DateElevator inspection
Needs Expiration DateVendor COI
Needs Expiration DateInsurance certificate
Needs Expiration DateReviewed records
Verified property facts
FOUNDRY RIDGE BOILER CO. · FR-240 · GAS-FIRED HOT WATER BOILER
Manufactured Jun 1, 2009 · 17 years old at finalization
Evidence: boiler-nameplate.heic, page 1CEDARLINE WATER HEATING · HW-80 · COMMERCIAL GAS WATER HEATER
Manufactured Mar 1, 2018 · 8 years old at finalization
Evidence: water-heater-nameplate.heic, page 1BACKFLOW PREVENTION ASSEMBLY TEST REPORT
Evidence: backflow-test-cert-prior-year.pdf, page 12-inch reduced pressure zone (RPZ), domestic water service
Evidence: backflow-test-cert-prior-year.pdf, page 1Clearline
Evidence: backflow-test-cert-prior-year.pdf, page 1CV-2000
Evidence: backflow-test-cert-prior-year.pdf, page 1PASS
Evidence: backflow-test-cert-prior-year.pdf, page 12024-05-23
Evidence: backflow-test-cert-prior-year.pdf, page 1Hudson Gate Backflow Testing
Evidence: backflow-test-cert-prior-year.pdf, page 1basement mechanical room
Evidence: backflow-test-cert-prior-year.pdf, page 1J. Okafor
Evidence: backflow-test-cert-prior-year.pdf, page 12024-05-23
Evidence: backflow-test-cert-prior-year.pdf, page 12 Millpond Lane, Tarrytown, NY 10591
Evidence: backflow-test-cert-prior-year.pdf, page 1Backflow Testing
Evidence: backflow-test-cert-prior-year.pdf, page 1Relief valve opened at 2.6 PSID. Check valve #1 held at 5.1 PSID.
Evidence: backflow-test-cert-prior-year.pdf, page 1PASS
Evidence: backflow-test-cert.pdf, page 12025-05-24
Evidence: backflow-test-cert.pdf, page 1J. Okafor
Evidence: backflow-test-cert.pdf, page 12025-05-24
Evidence: backflow-test-cert.pdf, page 1CV-2000
Evidence: backflow-test-cert.pdf, page 1basement mechanical room
Evidence: backflow-test-cert.pdf, page 1Backflow Testing
Evidence: backflow-test-cert.pdf, page 1Relief valve opened at 2.6 PSID. Check valve #1 held at 5.1 PSID.
Evidence: backflow-test-cert.pdf, page 12 Millpond Lane, Tarrytown, NY 10591
Evidence: backflow-test-cert.pdf, page 1Hudson Gate Backflow Testing
Evidence: backflow-test-cert.pdf, page 1BACKFLOW PREVENTION ASSEMBLY TEST REPORT
Evidence: backflow-test-cert.pdf, page 1Clearline
Evidence: backflow-test-cert.pdf, page 12-inch reduced pressure zone (RPZ), domestic water service
Evidence: backflow-test-cert.pdf, page 12009-08-01
Evidence: boiler-permit-card-2009.jpg, page 1FOUNDRY RIDGE
Evidence: boiler-permit-card-2009.jpg, page 1Final inspection
Evidence: boiler-permit-card-2009.jpg, page 1PASSED
Evidence: boiler-permit-card-2009.jpg, page 1KESTREL MECHANICAL SERVICES LLC
Evidence: boiler-permit-card-2009.jpg, page 12009-06-01
Evidence: boiler-permit-card-2009.jpg, page 1GAS-FIRED HOT WATER BOILER
Evidence: boiler-permit-card-2009.jpg, page 1FR-240
Evidence: boiler-permit-card-2009.jpg, page 1Palisade Elevator Inspection Co.
Evidence: elevator-cat1-cert.pdf, page 1Passenger traction elevator, 1 car, 4 landings + basement
Evidence: elevator-cat1-cert.pdf, page 1SATISFACTORY
Evidence: elevator-cat1-cert.pdf, page 1ELEVATOR PERIODIC TEST REPORT CATEGORY 1
Evidence: elevator-cat1-cert.pdf, page 1H. Vasquez
Evidence: elevator-cat1-cert.pdf, page 12025-08-26
Evidence: elevator-cat1-cert.pdf, page 12025-08-26
Evidence: elevator-cat1-cert.pdf, page 1Building: Stonegate Mills Apartments Address: 2 Millpond Lane, Tarrytown, NY 10591
Evidence: elevator-cat1-cert.pdf, page 142
Evidence: fire-alarm-inspection-cert (1).pdf, page 1Stonegate Mills Apartments, 2 Millpond Lane, Tarrytown, NY 10591
Evidence: fire-alarm-inspection-cert (1).pdf, page 1Sentry Ridge Fire Protection
Evidence: fire-alarm-inspection-cert (1).pdf, page 1FIRE ALARM SYSTEM — ANNUAL INSPECTION & TEST CERTIFICATE
Evidence: fire-alarm-inspection-cert (1).pdf, page 1PASS — all initiating and notification devices functional
Evidence: fire-alarm-inspection-cert (1).pdf, page 12026-05-28
Evidence: fire-alarm-inspection-cert (1).pdf, page 1No deficiencies noted at this inspection.
Evidence: fire-alarm-inspection-cert (1).pdf, page 1C. Braddock
Evidence: fire-alarm-inspection-cert (1).pdf, page 1Addressable fire alarm control panel
Evidence: fire-alarm-inspection-cert (1).pdf, page 1Granite Harbor Mutual
Evidence: kestrel-coi.pdf, page 1Kestrel Mechanical Services LLC
Evidence: kestrel-service-agreement.pdf, page 1Foundry Ridge FR-240 boiler; associated circulators and controls
Evidence: kestrel-service-agreement.pdf, page 12026-01-30
Evidence: kestrel-service-agreement.pdf, page 1Kestrel Mechanical Services LLC
Evidence: kestrel-combustion-report.pdf, page 1circulator pump bearing wear noted — monitor; vendor recommends scheduling replacement at a regular service visit.
Evidence: kestrel-combustion-report.pdf, page 12009-01-01
Evidence: kestrel-combustion-report.pdf, page 12025-11-22
Evidence: kestrel-combustion-report.pdf, page 1ANNUAL COMBUSTION & SAFETY SERVICE REPORT
Evidence: kestrel-combustion-report.pdf, page 12025-11-22
Evidence: kestrel-combustion-report.pdf, page 1PASS — unit serviceable
Evidence: kestrel-combustion-report.pdf, page 1circulator pump bearing wear noted — monitor; vendor recommends scheduling replacement at a regular service visit.
Evidence: kestrel-combustion-report.pdf, page 1L. Ferro
Evidence: kestrel-combustion-report.pdf, page 1gas-fired hot water boiler
Evidence: kestrel-combustion-report.pdf, page 1Foundry Ridge
Evidence: kestrel-combustion-report.pdf, page 1FR-24-09-3317
Evidence: kestrel-combustion-report.pdf, page 1FR-240
Evidence: kestrel-combustion-report.pdf, page 1Stonegate Mills Management Group
Evidence: management-agreement.pdf, page 1Stonegate Mills Apartments, 2 Millpond Lane, Tarrytown, NY 10591
Evidence: management-agreement.pdf, page 12025-01-27
Evidence: management-agreement.pdf, page 1GRANITE HARBOR MUTUAL
Evidence: property-policy-declarations.pdf, page 12025-06-24
Evidence: ray-note-roof-drain.jpg, page 1after big storms: clear N roof drain (leaves from the oak) takes 10 min w/ gloves
Evidence: ray-note-roof-drain.jpg, page 1boiler reset button — left side, red cover. if it locks out 2x CALL KESTREL, don't keep resetting
Evidence: ray-note-boiler-reset.jpg, page 1left side, red cover.
Evidence: ray-note-boiler-reset.jpg, page 1boiler reset button —
Evidence: ray-note-boiler-reset.jpg, page 1KESTREL
Evidence: ray-note-boiler-reset.jpg, page 12025-11-25
Evidence: ray-note-boiler-reset.jpg, page 1KESTREL
Evidence: ray-note-boiler-reset.jpg, page 1main shutoff — behind elec panel in old loading dock?? ask Ray (check before next leak!!)
Evidence: ray-note-shutoff.jpg, page 1Ray
Evidence: ray-note-shutoff.jpg, page 12026-06-26
Evidence: ray-note-shutoff.jpg, page 12025-12-26
Evidence: resident-email-2B-damp.pdf, page 1The damp smell near the kitchen ceiling in 2B is back — same corner that was patched last year.
Evidence: resident-email-2B-damp.pdf, page 1Hi Dana, The damp smell near the kitchen ceiling in 2B is back — same corner that was patched last year. No visible water this time, but it is noticeable after the weekend. Can someone take a look before it turns into another leak? Thanks, Marie (2B)
Evidence: resident-email-2B-damp.pdf, page 1kitchen ceiling in 2B
Evidence: resident-email-2B-damp.pdf, page 1M. Aiello
Evidence: resident-email-2B-damp.pdf, page 1Granite Harbor Mutual
Evidence: sentry-ridge-coi.pdf, page 1MECHANICAL ROOM — N END (boiler, domestic water service, RPZ)
Evidence: stonegate-mills-floor-plan-1988.pdf, page 14
Evidence: stonegate-mills-floor-plan-1988.pdf, page 1No unit isolation valves shown on this sheet.
Evidence: stonegate-mills-floor-plan-1988.pdf, page 142
Evidence: stonegate-mills-floor-plan-1988.pdf, page 1Domestic water service enters at basement mechanical room, north end.
Evidence: stonegate-mills-floor-plan-1988.pdf, page 1main roof
Evidence: roof-membrane-warranty.pdf, page 1Van Doren Roofing & Sheet Metal
Evidence: roof-membrane-warranty.pdf, page 12019-06-01
Evidence: roof-membrane-warranty.pdf, page 1Elevator
Evidence: vendor-contact-list.xlsx, page 1Palisade Elevator Inspection Co.
Evidence: vendor-contact-list.xlsx, page 1Two Rivers Electric LLC
Evidence: vendor-contact-list.xlsx, page 1Roofing
Evidence: vendor-contact-list.xlsx, page 1Fire alarm
Evidence: vendor-contact-list.xlsx, page 1Hudson Gate Backflow Testing
Evidence: vendor-contact-list.xlsx, page 1Boiler / HVAC
Evidence: vendor-contact-list.xlsx, page 1Sentry Ridge Fire Protection
Evidence: vendor-contact-list.xlsx, page 1Insurance
Evidence: vendor-contact-list.xlsx, page 1Pest control
Evidence: vendor-contact-list.xlsx, page 1Electrical
Evidence: vendor-contact-list.xlsx, page 1Greenbriar Pest Solutions
Evidence: vendor-contact-list.xlsx, page 1Calloway & Finch Insurance Brokerage
Evidence: vendor-contact-list.xlsx, page 1Backflow testing
Evidence: vendor-contact-list.xlsx, page 1Kestrel Mechanical Services LLC
Evidence: vendor-contact-list.xlsx, page 1Plumbing
Evidence: vendor-contact-list.xlsx, page 1Van Doren Roofing & Sheet Metal
Evidence: vendor-contact-list.xlsx, page 1Crossriver Plumbing & Heating Corp.
Evidence: vendor-contact-list.xlsx, page 1the hallway carpet was already wet
Evidence: resident-email-3B-leak.pdf, page 12B
Evidence: resident-email-3B-leak.pdf, page 1Thank you for getting the plumbers here so fast last night — the noise woke us around 2 AM and the hallway carpet was already wet.
Evidence: resident-email-3B-leak.pdf, page 1S. Prakash
Evidence: resident-email-3B-leak.pdf, page 12026-06-13
Evidence: resident-email-3B-leak.pdf, page 13B
Evidence: resident-email-3B-leak.pdf, page 1Annual inspection — PASS
Evidence: maintenance-ticket-log.xlsx, page 1EMERGENCY 2AM — stack failure, water in hall
Evidence: maintenance-ticket-log.xlsx, page 1Hall 2
Evidence: maintenance-ticket-log.xlsx, page 12026-07-07
Evidence: maintenance-ticket-log.xlsx, page 14C
Evidence: maintenance-ticket-log.xlsx, page 1Quarterly pest service
Evidence: maintenance-ticket-log.xlsx, page 12025-04-12
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Door closer adjusted
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 1Roof
Evidence: maintenance-ticket-log.xlsx, page 12025-06-09
Evidence: maintenance-ticket-log.xlsx, page 12025-03-14
Evidence: maintenance-ticket-log.xlsx, page 1Damp odor reported — monitoring
Evidence: maintenance-ticket-log.xlsx, page 12026-01-12
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 1Heating service agreement renewed
Evidence: maintenance-ticket-log.xlsx, page 1Kestrel Mechanical Services LLC
Evidence: maintenance-ticket-log.xlsx, page 12026-02-24
Evidence: maintenance-ticket-log.xlsx, page 1Basement
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 12026-03-31
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 1Two Rivers Electric LLC
Evidence: maintenance-ticket-log.xlsx, page 1Quarterly pest service
Evidence: maintenance-ticket-log.xlsx, page 11A
Evidence: maintenance-ticket-log.xlsx, page 12026-05-27
Evidence: maintenance-ticket-log.xlsx, page 12026-06-08
Evidence: maintenance-ticket-log.xlsx, page 1United Restoration Services
Evidence: maintenance-ticket-log.xlsx, page 1Ray's shutoff note filed — needs confirmation
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 1Ceiling stain kitchen — plumber called
Evidence: maintenance-ticket-log.xlsx, page 12025-08-28
Evidence: maintenance-ticket-log.xlsx, page 1Boiler annual combustion service
Evidence: maintenance-ticket-log.xlsx, page 1Crossriver Plumbing & Heating Corp.
Evidence: maintenance-ticket-log.xlsx, page 1Lintel repointing W elevation
Evidence: maintenance-ticket-log.xlsx, page 12025-10-24
Evidence: maintenance-ticket-log.xlsx, page 1Crossriver Plumbing & Heating Corp.
Evidence: maintenance-ticket-log.xlsx, page 1Backflow annual test
Evidence: maintenance-ticket-log.xlsx, page 13G
Evidence: maintenance-ticket-log.xlsx, page 1Quarterly pest service
Evidence: maintenance-ticket-log.xlsx, page 1Van Doren Roofing & Sheet Metal
Evidence: maintenance-ticket-log.xlsx, page 1Greenbriar Pest Solutions
Evidence: maintenance-ticket-log.xlsx, page 1Exterior
Evidence: maintenance-ticket-log.xlsx, page 12026-03-08
Evidence: maintenance-ticket-log.xlsx, page 1Greenbriar Pest Solutions
Evidence: maintenance-ticket-log.xlsx, page 1Entry door weatherstrip
Evidence: maintenance-ticket-log.xlsx, page 1Fire alarm
Evidence: maintenance-ticket-log.xlsx, page 12B/Hall
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 12026-06-18
Evidence: maintenance-ticket-log.xlsx, page 12B
Evidence: maintenance-ticket-log.xlsx, page 12025-09-12
Evidence: maintenance-ticket-log.xlsx, page 1Mechanical
Evidence: maintenance-ticket-log.xlsx, page 1Camera inspection recommended (see invoice)
Evidence: maintenance-ticket-log.xlsx, page 1Vendor
Evidence: maintenance-ticket-log.xlsx, page 1Quarry Lane Masonry
Evidence: maintenance-ticket-log.xlsx, page 11F
Evidence: maintenance-ticket-log.xlsx, page 1Handrail bracket tightened
Evidence: maintenance-ticket-log.xlsx, page 12025-07-16
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 1Wind damage check — seam lifted NE
Evidence: maintenance-ticket-log.xlsx, page 12025-12-28
Evidence: maintenance-ticket-log.xlsx, page 1Millpond Property Services
Evidence: maintenance-ticket-log.xlsx, page 1Snow/ice service
Evidence: maintenance-ticket-log.xlsx, page 14K
Evidence: maintenance-ticket-log.xlsx, page 12026-04-15
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 11J
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 12025-08-28
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 12025-11-30
Evidence: maintenance-ticket-log.xlsx, page 12025-03-02
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 12025-10-10
Evidence: maintenance-ticket-log.xlsx, page 1Radiator air-bleed
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Mechanical
Evidence: maintenance-ticket-log.xlsx, page 12025-03-28
Evidence: maintenance-ticket-log.xlsx, page 1Lobby
Evidence: maintenance-ticket-log.xlsx, page 12B
Evidence: maintenance-ticket-log.xlsx, page 12026-01-26
Evidence: maintenance-ticket-log.xlsx, page 1Millpond Property Services
Evidence: maintenance-ticket-log.xlsx, page 1Bathroom caulk renewed
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 12026-05-13
Evidence: maintenance-ticket-log.xlsx, page 1Sentry Ridge Fire Protection
Evidence: maintenance-ticket-log.xlsx, page 1Crossriver Plumbing & Heating Corp.
Evidence: maintenance-ticket-log.xlsx, page 1Paint touch-up after dry-down
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 1Elevator
Evidence: maintenance-ticket-log.xlsx, page 1Mailbox lock 2E replaced
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 12025-08-14
Evidence: maintenance-ticket-log.xlsx, page 1Stairwell B
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 1Dryer vent line cleaned
Evidence: maintenance-ticket-log.xlsx, page 12026-05-27
Evidence: maintenance-ticket-log.xlsx, page 12B/Hall
Evidence: maintenance-ticket-log.xlsx, page 12026-06-23
Evidence: maintenance-ticket-log.xlsx, page 1Greenbriar Pest Solutions
Evidence: maintenance-ticket-log.xlsx, page 1Hudson Gate Backflow Testing
Evidence: maintenance-ticket-log.xlsx, page 1Palisade Elevator Inspection Co.
Evidence: maintenance-ticket-log.xlsx, page 12025-12-14
Evidence: maintenance-ticket-log.xlsx, page 1Basement
Evidence: maintenance-ticket-log.xlsx, page 12025-09-26
Evidence: maintenance-ticket-log.xlsx, page 1Stack backup — emergency snake
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Basement
Evidence: maintenance-ticket-log.xlsx, page 1Intercom unit swapped
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 12026-04-29
Evidence: maintenance-ticket-log.xlsx, page 1Cleerflow Vent & Duct
Evidence: maintenance-ticket-log.xlsx, page 1PASS
Evidence: maintenance-ticket-log.xlsx, page 1United Restoration — mitigation: fans and dehumidifiers set, carpet lifted
Evidence: maintenance-ticket-log.xlsx, page 1Mechanical
Evidence: maintenance-ticket-log.xlsx, page 12026-07-15
Evidence: maintenance-ticket-log.xlsx, page 1Crossriver Plumbing & Heating Corp.
Evidence: maintenance-ticket-log.xlsx, page 1Category 1 annual test
Evidence: maintenance-ticket-log.xlsx, page 1Kestrel Mechanical Services LLC
Evidence: maintenance-ticket-log.xlsx, page 12025-11-16
Evidence: maintenance-ticket-log.xlsx, page 1Exterior
Evidence: maintenance-ticket-log.xlsx, page 13B
Evidence: maintenance-ticket-log.xlsx, page 1Hallway bulbs floor 3 replaced
Evidence: maintenance-ticket-log.xlsx, page 1Laundry room lint duct cleaned
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Window lock replaced
Evidence: maintenance-ticket-log.xlsx, page 1Laundry
Evidence: maintenance-ticket-log.xlsx, page 1Annual inspection
Evidence: maintenance-ticket-log.xlsx, page 12026-06-13
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Quarterly pest service
Evidence: maintenance-ticket-log.xlsx, page 1Backflow annual test
Evidence: maintenance-ticket-log.xlsx, page 1Category 1 annual test
Evidence: maintenance-ticket-log.xlsx, page 12025-02-15
Evidence: maintenance-ticket-log.xlsx, page 1Slop sink trap replaced
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 12025-10-23
Evidence: maintenance-ticket-log.xlsx, page 1Kitchen faucet washer
Evidence: maintenance-ticket-log.xlsx, page 12025-04-26
Evidence: maintenance-ticket-log.xlsx, page 12025-07-30
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Office
Evidence: maintenance-ticket-log.xlsx, page 1Ray
Evidence: maintenance-ticket-log.xlsx, page 1Greenbriar Pest Solutions
Evidence: maintenance-ticket-log.xlsx, page 12025-05-25
Evidence: maintenance-ticket-log.xlsx, page 1Water bill higher than usual — flagged
Evidence: maintenance-ticket-log.xlsx, page 1Greenbriar Pest Solutions
Evidence: maintenance-ticket-log.xlsx, page 12025-06-23
Evidence: maintenance-ticket-log.xlsx, page 1Quarterly pest service
Evidence: maintenance-ticket-log.xlsx, page 1Exterior
Evidence: maintenance-ticket-log.xlsx, page 12026-02-10
Evidence: maintenance-ticket-log.xlsx, page 1Snow/ice service
Evidence: maintenance-ticket-log.xlsx, page 1Board requested exposure summary
Evidence: maintenance-ticket-log.xlsx, page 12025-05-25
Evidence: maintenance-ticket-log.xlsx, page 1Panel directories re-labeled
Evidence: maintenance-ticket-log.xlsx, page 1Common
Evidence: maintenance-ticket-log.xlsx, page 1Equipment age is factual context, not a replacement instruction or failure prediction.
Approved invoices
Reviewed cost history
What the review covered
Records, scope, and limitations
- 2 Duplicates
- 1 Unsupported
stonegate-mills-site-plan.dwg: PropertyShield cannot read this file type (application/acad). Ask the customer to re-send it as a PDF, .docx, .xlsx, or a photo.
- stonegate-mills-site-plan.dwg: PropertyShield cannot read this file type (application/acad). Ask the customer to re-send it as a PDF, .docx, .xlsx, or a photo..
- This report reflects the records and observations in scope at finalization. It is not a code determination, engineering opinion, safety certification, insurance determination, or prediction of future loss.
Built, audited and authorized by Andrew Mason. AI-assisted extraction and drafting support the review; they do not make client-final decisions.
The nine-question Instant Readiness Diagnostic produces the PropertyShield Readiness Score. Verified Readiness Attainment counts separate URS-reviewed evidence checks. The two measures are never blended into one number.